What is Electric Transformer Mechanical Protection?

What is Electric Transformer Mechanical Protection?

Transformer protection is not just electrical, mechanical protection also is essential! What is transformer mechanical protection? , This is the article I will discuss today.

What is mechanical protection means?

Transformer protection is generally classified as mechanical protection that is carried out by detecting operational parameters such as the level of pressure/pressure gas evolution and temperature of the oil and winding.

The protection devices used on a particular Transformer are determined by the cost of the protection scheme concerning the possibility of a specific kind of failure and costs associated with replacing or fixing the transformer, and the chance of malfunction causing damage to the infrastructure or equipment is adjacent to it.

Why does transformer need mechanical protection?

Mechanical protection is essential to protect the transformer from swear damage in case of any fault related to the transformer’s mechanical mechanism. Identifying internal faults within the transformer using an extremely high degree of sensitivity is the main goal of Mechanical Protection.

This can lead to an immediate de-energization and simultaneously resist any external damage within the transformer, i.e., faults. De-energisation and sensing reasons to be the damage from defects and the need for repairs to be minimized.

 However, it must be able to offer backup protection in the event of faults that affect the system as they could cause deterioration, rapid aging, or even loss of the transformer’s insulation as a result of over-heating and force of impact that is generated in the windings as a result of the high currents of fault.

Alongside internal faults that can occur, system malfunctions such as excessive excitation, over-voltage, and lack of cooling may result in deterioration and then accelerated aging or failure within the transformer. Therefore, its essential to protect the transformers against these issues.

What are the mechanical protections in power transformers?

Four types of devices are used in terms of the mechanical protection of power transformers.

  1. Buchholz (Gas) Relay
  2. Pressure Relay
  3. Oil Level Monitor Device
  4. Winding Thermometer

Buchholz (Gas) Relay:

Buchholz protection is a mechanical fault detection device for electric malfunctions in transformers with oil immersion.

Buchholz (gas) relays are positioned in the piping between the transformer‘s main tank and the oil conservator. The conservator pipe must be inclined slightly to ensure the most reliable operation.

There is often the bypass pipe which makes it possible to remove the Buchholz relay out of operation.

Buchholz Protection Relay is a quick and sensitive fault detection device. It functions independently of the transformer’s number of windings, the position of the tap changer, and the transformer’s instruments.

When the tap changer is of the on-tank (container) kind, with an oil conservator, there’s an individual Buchholz relay to the tap changer.

An average Buchholz protection consists of a pivoted floating (F) and a pivoted vane (V). The float holds one mercury switch while the vane has another mercury switch. Usually, the casing gets lined with oil, and the mercury switches are opened.

If there is a minor fault:

This assumes that a minor fault happens in the transformerGases produced by minor faults are released from the point of fault up towards the top of the transformer.

The gas bubbles will pass through the piping until they reach the conservator. The gas bubbles will then be trapped inside the casing of Buchholz protection.

This is because the gas will replace the oil in the casing. As the oil level decreases, the float (F) will flow, and the mercury switch is tilted and shuts off an alarm circuit.

When a major Fault occurs:

Suppose that a major fault occurs inside the transformer either to earth or between windings or phases. Such faults rapidly result in large amounts of gases (more than 50 cm3/(KWS) and oil vapor that cannot be escaped.

They result in a theatrical increase in pressure and displace oil. This creates an immediate flow of gas from the transformer to the conservator.

The vane (V) reacts to a high gas and oil flow through the pipe to the conservator. In this situation, the mercury switch shuts off the trip circuit. The operation time of the trip contacts is contingent on the area where the fault occurs and the volume of the fault’s current.

Pressure Relay:

Many power transformers equipped with an on-tank type tap changer come with automatic pressure control for the tap changer’s separate oil compartment.

This safeguard detects a sudden pressure increase within the tap changer’s oil enclosure.If the piston’s front-end pressure is higher than the spring’s counter force, the piston will move, activating the switches. The micro switch in the switch unit is sealed hermetically and is pressurized by nitrogen gas.

The simplest type used for pressure relief devices is the commonly used frangible disk. The surge of oil triggered by a severe internal fault ruptures the disk and permits the oil to flow out quickly. Reducing and easing the pressure increase prevents an explosive rupture of the tank, causing the fire.

Using a separate tap changer, the oil enclosure could be equipped with a pressure relief device.

The device for pressure relief can be outfitted with a contacts unit to indicate circuit breaker(s) tripping circuits.The disadvantage of the frangible disk is that the oil that remains inside the tank is exposed to air following the rupture.

This is prevented by the more efficient valve for pressure relief, which is opened to allow the release of oil when the pressure is higher than the pre-adjusted limit.

If the pressure in the area is enormous, this spring-controlled valve will operate in just a few milliseconds. It can also provide quick tripping if the correct contacts are installed. The valve shuts down automatically when the internal pressure drops below a threshold.

Oil Level Monitor Device:

Transformers equipped with an oil conservator(s) (expansion tank) typically come with an oil monitor. Typically, the monitor has two contacts to signal alarm. One is for the maximum oil level alarm, and the other is for a minimum oil level alarm.

The top-oil thermometer has an insulated bulb for a liquid thermometer inside a pocket near the top of the transformer. The thermometer measures the temperature of the oil at the top of the transformer. The thermometer with the highest temperature could contain one to four contacts that are closed sequentially as they reach greater temperatures.

The temperature of the top-oil can be significantly less than the winding temperature, particularly after a sudden increase in load. This implies that the thermometer on top of the oil is not a reliable protection against overheating.

If the rules regarding transformers’ life expectancy loss allow, tripping on top-oil temperature could be acceptable. This is in addition to the advantage of directly monitoring the oil’s temperature to ensure that it doesn’t exceed the flash temperature.

Winding Thermometer:

A winding thermometer reacts to the temperature at the top of the oil and the heat effect of load current.A winding thermometer produces an image showing the hot section part of the winding. 

The top-oil temperature is measured using the same procedure that was previously described. This measurement can be further enlarged by a current signal that is in proportion to the load current inside the winding.

The current signal comes from a current transformer found inside the bushing of this particular winding. This current leads to a resistor element in the central unit.

This resistor heats up, and as a result of the current flowing through it, it will, in its turn, heat the measurement below, resulting in an increased indicator movement.

The bias in temperature corresponds to the resistivity of an electric heating (resistor) element.

The outcome of the heat run will provide the data to alter the resistance and, consequently, it is possible to adjust the bias of temperature. The preference should be proportional to the difference between hot spots and top-oil temperatures.

The time constant of the pocket’s heating should coincide with the time constant of the winding’s heat.The temperature sensor will then measure the temperature to be equivalent to the winding temperature when the bias is the same as the temperature differential and the time constants.

With four contacts, the two lower levels are employed to turn on pumps or fans to force cooling, the fourth level to trigger an alarm, and the 4th to activate breakers for load or shutting off the transformer, or both.

If a power transformer is equipped with top-oil thermometers and winding thermometers, the latter handles forced cooling control.

Install my Free Electrical android Apps